Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve. The valve shall be sealed and tagged after the category 5 test. 7/22/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 4/1/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational when the 120 volt power source is removed. 4/1/2022
A17.1-1996 : Elevators 1.3 - Operating control devices 1001.2(a)(3) Repair or replace the door close button. 4/1/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/1/2022