MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in machine room
|
11/15/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be on display in the machine room
|
11/16/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current state operating certificate shall be properly displayed in machine room.
|
11/16/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Elevator lobby smoke detectors do not appear to be connected to elevator controller and no detector in basement lobby. Red tagged elevator.
|
12/28/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Elevator lobby smoke detectors do not appear to be conneted to elevator controller and no dector in basement lobby
|
11/9/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Existing phone works, but goes to different contractor. Reprogram as needed.
|
1/10/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door lock shall be repaired to work correctly
|
11/15/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Phase I operations failed, car was red tagged and removed from service.
|
1/10/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone works, needs reprogram to talk to operators(asking for keypad operation)
|
11/6/2024
|
conversion
|
conversion
|
n/a
|
|
|
Pit light not working
|
11/16/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light shall work.
|
11/15/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light shall work.
|
11/15/2023
|
conversion
|
conversion
|
n/a
|
|
|
Pit must be kept clean and dry
|
11/16/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State certiicate in machine room
|
11/15/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove water from pit
|
11/15/2023
|
conversion
|
conversion
|
n/a
|
|
|
Repair emergency phone
|
11/16/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Repair pit light
|
11/15/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Significant ground water entering pit. Provide means to prevent.
|
11/15/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Simulated FAID on controller, no response.
|
1/10/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Sump pump hole shall be covered.
|
11/15/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Sump pump hole shall have a cover.
|
11/15/2023
|