Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Have the emergency phone repaired as there is no dial tone. 10/22/2021
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) Have the fire extinguisher re-certified as it expired in 2020 10/22/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room. 8/16/2019
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Provide a maintanence control program in the machine room. 10/22/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Red Tag) x x Repair the emergency phone as the incomming line is dead. 8/12/2019
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.11.3.1.5(c) REplace both jack cylinder packings as both are leaking excessivily. 10/22/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Red Tag) x x The emergency phone has no dial tone. 8/2/2019