A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
8.11.3.1.2(b)
|
|
|
Door closure and door know need to be replaced
|
12/6/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit has standing water and mold floating around in it. Needs to be cleaned and pumped out and way to mitigate water collection
|
12/6/2023
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
In Case of Fire signs need to be placed by Hall call buttons
|
12/6/2023
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Overspeed valve is not sealed. Full load test will be required next year to test and reseal the valve
|
12/6/2023
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
Door closure needs to be installed.
|
12/6/2023
|