Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Post Mo State operating permit in machine room 10/19/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Need testing procedures in MCP on or before 1/1/22 5/22/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room Overspeed valve set at 171 2/10/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x Front and rear restrictors shall work. 7/3/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x Machine room fire extinguisher shall be permanently mounted to the wall. 7/3/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Lighting disconnect fused improperly. Replace 20A fuse with proper 15A. 7/3/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Hall calls shall work. 7/3/2025
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems x Adjust upthrusts for proper clearances (2nd floor front). 7/3/2025
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems x Adjust upthrusts for proper lower gap opening. 7/3/2025
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches x Adjust hoistway access limit (PIT) for proper stopping heights. 7/3/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x INCOMPLETE: Remaining testing needed is as follows: pump pressures and speed, relief pressure, OSV, rear door torque, phase I & II fire service, FAID and recalls, battery lowering, COP stop, low oil, and 15 min static testing. 7/3/2025