Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No 2-WAY COMMUNICATION DEVICE SHALL WORK. No Answer
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.2 No No Investigate and repair the source of the grinding noise at the hoist machine.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. There are no schematics, on-site(as well as fault code lists and parameter tables)
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 201 No No Need to change worn/damaged upper car roller guides and lower counterweight roller guides.
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 210.13 No No Replace missing/damaged/faded "Do not use elevator in case of fire" Signage on multiple floors.
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 210.13 No No Replace damaged Phase 2 instructions inside car.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No Pit shall be kept clean. Remove excess debris
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No Provide MCP 7/7/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Provide testing 7/7/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Emergency Power was not transferred to the elevator during testing 7/7/2022
A17.1-1996 : Elevators 4.12 - Standby power selection switch 1002.2g No No Provide testing 7/17/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 7/11/2024
A17.1-1996 : Elevators 3.23 - Suspension rope 212 Yes No Ropes are rusted and undersized, need to replace all hoist ropes. Re-inspection required 7/12/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/9/2025