A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
4/22/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
4/22/2021
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
4/22/2021
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room door shall be self-closing and self-locking.
|
5/13/2025
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5c Receptacles
|
|
|
Machine room GFCI outlet not working.
|
5/13/2025
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Non-elevator related items shall not be stored in machine room.
|
5/13/2025
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Provide a code compliant, current tested fire extinguisher in the elevator machine room.
|
9/16/2019
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
1001.2(b)(4)
|
|
|
Remove the black mold from the machine room wall.
|
9/16/2019
|
A17.1-1996 : Elevators
|
1.12 - Car enclosure
|
207.4
|
|
|
Tighten/repair car interior handrail.
|
5/13/2025
|