MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not call an active line. Re-inspect required
|
11/2/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency two way communication phone does not work. Repair and reinspect
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Replace hydraulic fluid, pump unit contaminated with water
|
3/16/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Repair machine room lighting. Only one lamp working out of 4.
|
3/8/2023
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Replace hydraulic fluid in pump unit contaminated with water
|
3/16/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Repair Phase II fire recall. Stop switch not overridden when car is returned to Phase I from Phase II. Did not red tag. Reinspect only.
|
11/24/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Fire service returns to the wrong floor on initial recall. Re-inspection required
|
11/2/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Emergency stop switch in the elevator shall be overridden in Phase II recall. Re-inspection required
|
2/14/2023
|