Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone does not call an active line. Re-inspect required 11/2/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency two way communication phone does not work. Repair and reinspect
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Repair machine room lighting. Only one lamp working out of 4. 3/8/2023
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Replace hydraulic fluid in pump unit contaminated with water 3/16/2023
MO Minimum : Elevators (S) - Fire Service (S)1 x x Repair Phase II fire recall. Stop switch not overridden when car is returned to Phase I from Phase II. Did not red tag. Reinspect only. 11/24/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire service returns to the wrong floor on initial recall. Re-inspection required 11/2/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Emergency stop switch in the elevator shall be overridden in Phase II recall. Re-inspection required 2/14/2023