Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers procedure inside machine 12/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) Fire recall switch needs to be provided with visual signal to indicate elevator is on fire recall operation 12/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 2.16.3.1 Capacity Plates The Capacity Plate in elevator is unreadable must be replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency Telephone not functioning. Buildings are going to a Digital telephone system on all cars. System has not been initiated. Emergency Alarm Bell works. 10/9/2024