ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.16.8
|
x
|
x
|
Brake Failed to hold 125%
|
4/8/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
Must Make Bottom Landing Hoistway Access Key Switch operable. 8.6.4.14
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
Must make Fire service Phase I instructional sign readable. 8.11.2.1.1(o)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
Must make In case of fire do not use Elevator signs Readable. 8.11.2.1.1(o)
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No Records
|
6/28/2022
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(j)
|
|
|
Out 0f Date
|
4/9/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone failed
|
5/10/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone Failed
|
7/11/2024
|