Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.23 - Suspension rope 212 x Suspension ropes are below minimum diameter and rouged, need to be replaced. Re-inspection required 2/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x All door guides shall have fire tabs bent down to engage sill or install separate fire tabs (4th & 5th Floors). 11/9/2023
A17.1-1996 : Elevators 1.4 - Sills and car floor 204.2(a) Material for Car Enclosure Linings, and floor Coverings. The cab flooring is buckling, posing possible tripping hazard. Take corrective action as needed. 11/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates COP shall have car number displayed. 11/9/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service shall be tested monthly and properly documented in MCP log sheet. 11/9/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Compliant/Required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures. 11/9/2023