(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
All door guides shall have fire tabs bent down to engage sill or install separate fire tabs (4th & 5th Floors).
|
11/9/2023
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Compliant/Required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, oil log, & evacuation procedures.
|
11/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
COP shall have car number displayed.
|
11/9/2023
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Fire service shall be tested monthly and properly documented in MCP log sheet.
|
11/9/2023
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
212
|
x
|
|
Suspension ropes are below minimum diameter and rouged, need to be replaced. Re-inspection required
|
2/17/2023
|
A17.1-1996 : Elevators
|
1.4 - Sills and car floor
|
204.2(a) Material for Car Enclosure Linings, and floor Coverings.
|
|
|
The cab flooring is buckling, posing possible tripping hazard. Take corrective action as needed.
|