Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2 On-Site Documentation Ventilation and other equipment added and/or modified on car top shall comply with code. 5/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire Use Stairs” is missing. Install signage that conforms to the building code this elevator was installed to meet. 11/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for "In case of fire use stairs" is missing on several floors. Install signage that conforms to the building code this elevator was installed to meet. 11/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for "In case of Fire use Stairs" is missing, need to install signage 9/5/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x The elevator hoisting ropes are not the correct type of of lay for this elevator sheave. The correct rope is of “lang lay” construction as required by the manufacture. The ropes shall be replaced with the correct ropes specified by the manufacturer. Reinspection in 60 days. 6/2/2022