A17.1-1996 : Elevators
|
4.10 - Emergency doors blind hoistway
|
1001.2(d)(10)
|
x
|
|
To fully comply with the 3rd floor to be an emergency door, the following shall be addressed. Interlock on hoistway door must be functional, and accessible on the landing side with a special key. Lobby side door shall be marked with "2" in high letters saying "danger, elevator hoistway".
|
12/10/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
12/10/2020
|
A17.1-1996 : Elevators
|
4.10 - Emergency doors blind hoistway
|
1001.2(d)(10)
|
x
|
|
To fully comply with the 3rd floor to be an emergency door, the following shall be addressed. Accessible on the landing side with a special key. Lobby side door shall be marked with "2" in high letters saying "danger, elevator hoistway".
|
8/4/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
3/30/2023
|
A17.1-1996 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
100.6
|
|
|
Bevel ledge in hoistway at first floor.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication inoperable. Re-inspection required
|
|
conversion
|
conversion
|
n/a
|
|
|
The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
|
11/23/2020
|
conversion
|
conversion
|
n/a
|
|
|
The electrical disconnect switch is missing a cover plate exposing the inner electrical panel. Reinstall the missing cover plate.
|
11/23/2020
|
conversion
|
conversion
|
n/a
|
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone for proper operation and passenger safety.
|
11/23/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light is not working, needs repaired/replaced
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate
|
10/20/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair emergency phone re-inspection in 15 days Friday (4/14/23). Car will be removed from service at this time if not repaired. This is the 4th year this violation has been submitted.
|
4/15/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher is expired, have serviced or replaced
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
No lockable disconnect in machine room
|
|