Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 11/23/2020
conversion conversion n/a No No The electrical disconnect switch is missing a cover plate exposing the inner electrical panel. Reinstall the missing cover plate. 11/23/2020
conversion conversion n/a No No The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone for proper operation and passenger safety. 11/23/2020
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No No lockable disconnect in machine room 10/28/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate 10/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher is expired, have serviced or replaced 10/28/2025
A17.1-1996 : Elevators 3.13 - Windows, projections, recesses, and setbacks 100.6 No No Bevel ledge in hoistway at first floor. 10/28/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light is not working, needs repaired/replaced 10/28/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in machine room 3/11/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher is expired, have serviced or replaced 3/11/2026
A17.1-1996 : Elevators 3.13 - Windows, projections, recesses, and setbacks 100.6 No No Bevel ledge in hoistway at first floor. 3/11/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light is not working, needs repaired/replaced 3/11/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Provide means for pit light to be operational.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in machine room 10/28/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 3/11/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Means of two way communication are inoperable and shall be repaired.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No At this time the car door restrictor is failing to operate and shall be repaired or replaced.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 10/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair emergency phone re-inspection in 15 days Friday (4/14/23). Car will be removed from service at this time if not repaired. This is the 4th year this violation has been submitted. 4/15/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable. Re-inspection required 3/30/2023
A17.1-1996 : Elevators 4.10 - Emergency doors blind hoistway 1001.2(d)(10) Yes No To fully comply with the 3rd floor to be an emergency door, the following shall be addressed. Interlock on hoistway door must be functional, and accessible on the landing side with a special key. Lobby side door shall be marked with "2" in high letters saying "danger, elevator hoistway". 12/10/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 12/10/2020
A17.1-1996 : Elevators 4.10 - Emergency doors blind hoistway 1001.2(d)(10) Yes No To fully comply with the 3rd floor to be an emergency door, the following shall be addressed. Accessible on the landing side with a special key. Lobby side door shall be marked with "2" in high letters saying "danger, elevator hoistway". 8/4/2021