Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Static test failure. Need to check valve. 2.42 2/6/2019
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)1 Packing is leaking. Needs to be replaced. REINSPECTION REQUIRED. 4/12/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV not sealed. Perform test on or before next annual inspection date. 4/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No MCP. 1/12/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire panel was replaced and programmed faid devices shall be tested in the presence of a licensed elevator inspector 11/21/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not calling out. Repair as needed - Reinspection required 11/21/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x x Smoke detector in machine room does not put elevator into phase I. Smoke detector shall put elevator into phase I and send elevator to alternate floor. Red-tagged until repaired. Re-inspection required 12/4/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Close machine room penetrations to maintain fire rating. 12/5/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Install currently serviced fire extinguisher in the elevator machine room 12/5/2024