A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Install currently serviced fire extinguisher in the elevator machine room
|
12/5/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire panel was replaced and programmed faid devices shall be tested in the presence of a licensed elevator inspector
|
11/21/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not calling out. Repair as needed - Reinspection required
|
11/21/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
x
|
Smoke detector in machine room does not put elevator into phase I. Smoke detector shall put elevator into phase I and send elevator to alternate floor. Red-tagged until repaired. Re-inspection required
|
12/4/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Static test failure. Need to check valve. 2.42
|
2/6/2019
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)1
|
|
|
Packing is leaking. Needs to be replaced. REINSPECTION REQUIRED.
|
4/12/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV not sealed. Perform test on or before next annual inspection date.
|
4/12/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
No MCP.
|
1/12/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Close machine room penetrations to maintain fire rating.
|
12/5/2024
|