Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)13 Repair the hole in the hoistway at the basement level.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Replace the missing cab light bulb and properly guard lights.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC type fire extinguisher shall be kept in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods A tool to reset the car safeties shall be available on-site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x The car door restrictor shall be operational. 7/5/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency telephone shall be operational. 7/5/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Repair the hole in the hoistway at the basement.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates 110V disconnect shall be labeled. Where there is more than one machine in a room, the disconnect for each machine shall be conspicuously numbered to correspond to the machine it controls.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 4/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Replace faded "Do not use elevator in case of fire" signage as needed. 4/17/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Condensation dripping on duct work. All pipes conveying liquid, vapor, or gas that are above or come near elevator equipment shall be guarded or guttered.
MO Minimum : Elevators (H) - Machine Rooms (H)2 All pipes conveying liquid, vapor, or gas that are above or near any elevator equipment shall be guarded or guttered.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Provide code compliant machine room door handle and lock.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit lighting shall be operational.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Rope used as a connection from the safety to the governor rope, including rope wound on the safety-rope drum, shall be made of metal, and shall be corrosion resistant (currently iron/steel). Replace and retest for soft set and pullout length. 4/17/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x x Door reopening devices that are sensitive to smoke shall be rendered inoperative on Firemans' Return service. 9/22/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x The electronic safety edge is not bypassed on Phase 1 fire recall. Take corrective action. 7/5/2022
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x Car door restrictor shall work at all floors.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. Button lights up, but does not dial (communication loss works).
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Could not test windup safeties. A tool to reset the car safeties shall be available on-site. 2/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The test is incomplete. Fire service, testing of light/alarm/phone with 110V source removed, inspection of pit, inspection of door restrictor, and inspection of hoistway need to be completed. 2/14/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x 2.3.1 - Machine room lighting needs to be repaired. One or more bulbs is not working. 4/17/2024
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Machine room climate control is non-functional. 10/8/2024
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems x Replace missing secondary fire tab on top of 12th floor hoistway door. 4/17/2024
conversion conversion conversion - reinspect x Cover hole in hoistway at basement level. 10/18/2018
conversion conversion n/a Replace missing cab light bulb and properly guard lights.
conversion conversion n/a There shall be a light in the pit.
conversion conversion conversion - reinspect x Car door restrictor shall work. 10/18/2018
conversion conversion conversion - reinspect x In cab emergency telephone shall work. 10/18/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.