Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display the current state operating certificate.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
conversion conversion conversion - reinspect Yes No Cover hole in hoistway at basement level. 10/18/2018
conversion conversion conversion - reinspect Yes No Car door restrictor shall work. 10/18/2018
conversion conversion conversion - reinspect Yes No In cab emergency telephone shall work. 10/18/2018
conversion conversion n/a No No Replace missing cab light bulb and properly guard lights.
conversion conversion n/a No No There shall be a light in the pit.
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems Yes No Replace missing secondary fire tab on top of 12th floor hoistway door. 4/17/2024
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 Yes No Machine room climate control is non-functional. 10/8/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No 2.3.1 - Machine room lighting needs to be repaired. One or more bulbs is not working. 4/17/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Could not test windup safeties. A tool to reset the car safeties shall be available on-site. 2/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The test is incomplete. Fire service, testing of light/alarm/phone with 110V source removed, inspection of pit, inspection of door restrictor, and inspection of hoistway need to be completed. 2/14/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. Button lights up, but does not dial (communication loss works).
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No Car door restrictor shall work at all floors.
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Door reopening devices that are sensitive to smoke shall be rendered inoperative on Firemans' Return service. 9/22/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No The electronic safety edge is not bypassed on Phase 1 fire recall. Take corrective action. 7/5/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Rope used as a connection from the safety to the governor rope, including rope wound on the safety-rope drum, shall be made of metal, and shall be corrosion resistant (currently iron/steel). Replace and retest for soft set and pullout length. 4/17/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit lighting shall be operational.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Condensation dripping on duct work. All pipes conveying liquid, vapor, or gas that are above or come near elevator equipment shall be guarded or guttered.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No All pipes conveying liquid, vapor, or gas that are above or near any elevator equipment shall be guarded or guttered.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Provide code compliant machine room door handle and lock.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No The car door restrictor shall be operational. 7/5/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 4/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency telephone shall be operational. 7/5/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No A tool to reset the car safeties shall be available on-site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Repair the hole in the hoistway at the basement.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No An ABC type fire extinguisher shall be kept in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No 110V disconnect shall be labeled. Where there is more than one machine in a room, the disconnect for each machine shall be conspicuously numbered to correspond to the machine it controls.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Yes No Replace faded "Do not use elevator in case of fire" signage as needed. 4/17/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Replace the missing cab light bulb and properly guard lights.
MO Minimum : Elevators (A) - Hoistways (A)13 No No Repair the hole in the hoistway at the basement level.