MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car shall work. Re-inspection required
|
5/6/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car shall work.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Light fixture in machine room has burned out bulbs. Replace same to provide at least 10 fc illumination at floor.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Light fixture in machine room has two burned out bulbs, replace same to provide at least 10 fc illumination at floor
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Overspeed governor rope is damaged and has breaks, need to replace rope. Red-tagged, Re-inspection required
|
5/6/2024
|
A17.1-1996 : Elevators
|
1.3 - Operating control devices
|
1001.2(a)(3)
|
|
|
Phone light indicator bezel in elevator cab is broken. Repair
|
3/29/2023
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Replace burnt out lights in elevator machine room.
|
5/3/2023
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
1001.2(c)(26)
|
x
|
|
Governor rope pull through force is 700 lbs. Govenor nameplate is 400 lbs maximum. Replace/repair.
|
12/6/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
5/3/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
5/3/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
All fire service keys for elevators in one building shall be keyed alike. Re-inspection required
|
3/10/2023
|