Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired, have serviced or replaced
A17.1-1996 : Elevators 3.20 - Governor rope 1001.2(c)(26) x Governor rope pull through force is at least 800 lbs. Nameplate is 400 lbs maximum. Repair/replace. 3/9/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Incomplete inspection - conduct safety test with rated load/speed, car buffer and brake test. 3/9/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 5/3/2023
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys All fire service keys for elevators in one building shall be keyed alike. 5/3/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 5/3/2023
MO Minimum : Elevators (I) - Pits (I)1 Clean trash & debris from elevator pit 5/3/2023