MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired, have serviced or replaced
|
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
1001.2(c)(26)
|
x
|
|
Governor rope pull through force is at least 800 lbs. Nameplate is 400 lbs maximum. Repair/replace.
|
3/9/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Incomplete inspection - conduct safety test with rated load/speed, car buffer and brake test.
|
3/9/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
5/3/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
|
|
All fire service keys for elevators in one building shall be keyed alike.
|
5/3/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
5/3/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean trash & debris from elevator pit
|
5/3/2023
|