Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting 1) Elevator machine room shall have adequate lighting. The light over by the controller portion of the hydraulic pump unit went out or quit working. 3/10/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a 1) All pits shall be kept dry and clean. The pit has a lot of water on the floor. 7/27/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) 1. A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program (8.6.1.2.1), other tests (see 8.6.1.2.2), examinations and adjustments, and the specified scheduled intervals shall be maintained. 5/6/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.2 Callbacks (Trouble Calls) Documentation 2. A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. 5/6/2021
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 3. Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load. Due for 5-year testing. Ref: 8.6.5.16.5 Note: This Shall Be Done Next Year, during the annual inspection. 5/6/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/26/2024