MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
|
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
10/31/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
A grease seal on the drive machine is leaking excessively and shall be replaced.
|
7/10/2020
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Standby power needs to be tested. Re-inspection required
|
11/15/2023
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
Sprinkler heads have been added to the elevator machine room without the required heat detectors to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect.
|
7/10/2020
|
A17.1-1996 : Elevators
|
2.19 - Gears, bearings, and flexible couplings
|
1001.2(b)(17) - no reinspect
|
|
|
A grease seal on the drive machine is leaking excessively and shall be replaced.
|
7/10/2020
|
conversion
|
conversion
|
n/a
|
|
|
A grease seal on the drive machine is leaking excessively and shall be replaced.
|
7/10/2020
|
conversion
|
conversion
|
n/a
|
|
|
The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch.
|
7/10/2020
|