Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 10/31/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements A grease seal on the drive machine is leaking excessively and shall be replaced. 7/10/2020
A17.1-1996 : Elevators 2.19 - Gears, bearings, and flexible couplings 1001.2(b)(17) - no reinspect A grease seal on the drive machine is leaking excessively and shall be replaced. 7/10/2020
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 Sprinkler heads have been added to the elevator machine room without the required heat detectors to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect. 7/10/2020
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Standby power needs to be tested. Re-inspection required 11/15/2023
conversion conversion n/a A grease seal on the drive machine is leaking excessively and shall be replaced. 7/10/2020
conversion conversion n/a The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. 7/10/2020