A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
Elevator equipment room door needs to be self closing and self locking.
|
12/5/2023
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
Need 'In Case of Fire" signs at each floor
|
12/5/2023
|
A17.1-1996 : Elevators
|
1.19 - Car Ride
|
1001.2(a)(19)
|
|
|
Several guide rollers are worn and need replacement soon
|
12/5/2023
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
Both top and Bottom hoistway access key switches must be made Operable. 8.6.4.14
|
|
conversion
|
conversion
|
n/a
|
|
|
Motor mount, buffer channels etc. severely corroded from water in the pit. Needs attention soon.
|
8/18/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone needs to be programmed to working number
|
3/23/2022
|