Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (F) - Electrical Switches (F)2 x All electric elevators shall have final limit switches installed at the top of the hoistway and the bottom of the hoistway. 9/17/2021
MO Minimum : Elevators (F) - Electrical Switches (F)2 x Unit shall have bottom final limit switch.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) All onsite documents shall be provided in machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Clean up oil and grease from floor and bed plate 10/2/2018
MO Minimum : Elevators (H) - Machine Rooms (H)4 There is an excessive amount of oil and grease on the machine room floor and bed plate. The oil and grease shall be cleaned up and a catch pan installed to minimize a potential hazard.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
MO Minimum : Elevators (J) - Counterweights (J)1 Add counterweight to car gate to maintain full open. 10/2/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.