Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Clean up oil and grease from floor and bed plate 10/2/2018
MO Minimum : Elevators (J) - Counterweights (J)1 No No Add counterweight to car gate to maintain full open. 10/2/2018
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes No All electric elevators shall have final limit switches installed at the top of the hoistway and the bottom of the hoistway. 9/17/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No There is an excessive amount of oil and grease on the machine room floor and bed plate. The oil and grease shall be cleaned up and a catch pan installed to minimize a potential hazard.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (F) - Electrical Switches (F)2 Yes No Unit shall have bottom final limit switch.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No All onsite documents shall be provided in machine room.