Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Car door restrictor does not function 9/16/2022
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Electrical supply wiring for machine room air conditioner needs to be in metal conduit. Remove 20 foot extension cord that runs across the machine room floor 1/3/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate. 9/16/2022
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room access door needs to be self-locking and non-defeatable. 1/3/2024
A17.1-1996 : Elevators 2.14 - Code data plate 215 Post code data plate on controller or disconnect. "ASME A17.1 1996" 1/3/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room. 1/3/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 9/29/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room access door needs to be self-locking and non-defeatable 1/3/2024
A17.1-1996 : Elevators 2.14 - Code data plate 215 Post code data plate on controller or disconnect 1/3/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed in machine room 1/3/2024
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Electrical power feed for machine room air conditioner need tobe in conduit. 1/3/2024
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space Remove debris and rubbish from machine room floor 1/3/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 9/24/2021
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.19.16 x Car door restrictor does not function 9/24/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certficate inside machine room 1/3/2024
MO Minimum : Elevators (I) - Pits (I)1 Debris in pit, clean. 10/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not connecting.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Replace all worn counterweight rollers. 10/29/2024