MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Need to replace illegible fire service Phase I key switch bezel located in the lobby.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Phase I key switch bezel wording is missing, needs to be replaced
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency battery lowering device is not working. Re-inspection required
|
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
Overspeed valve is not sealed. Perform test, tag and seal upon completion within (90) days.
|
7/19/2021
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.14.2
|
x
|
|
During 15 minute standing test, car sank onto car buffers. Hydraulic system is leaking fluid in either the underground piping or hydraulic jack. Elevator removed from service.
|
7/19/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency battery lowering device is not working. Re-inspection required
|
7/31/2024
|