Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No Overspeed valve is not sealed. Perform test, tag and seal upon completion within (90) days. 7/19/2021
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.14.2 Yes No During 15 minute standing test, car sank onto car buffers. Hydraulic system is leaking fluid in either the underground piping or hydraulic jack. Elevator removed from service. 7/19/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emergency battery lowering device is not working. Re-inspection required 7/31/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emergency battery lowering device is not working. Re-inspection required 8/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Need to replace illegible fire service Phase I key switch bezel located in the lobby. 6/20/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Phase I key switch bezel wording is missing, needs to be replaced 6/20/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current state operating certificate shall be displayed inside of the elevator Machine room. 9/4/2025