Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Phase I key switch bezel wording is missing, needs to be replaced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Need to replace illegible fire service Phase I key switch bezel located in the lobby.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency battery lowering device is not working. Re-inspection required 7/31/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency battery lowering device is not working. Re-inspection required
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.14.2 x During 15 minute standing test, car sank onto car buffers. Hydraulic system is leaking fluid in either the underground piping or hydraulic jack. Elevator removed from service. 7/19/2021
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Overspeed valve is not sealed. Perform test, tag and seal upon completion within (90) days. 7/19/2021