A17.1-1996 : Elevators
|
2.34 - Flexible Hydraulic Hose and Fitting Assemblies
|
303.3c
|
x
|
x
|
Hydraulic oil line fitting is leaking excessively, needs to be replaced. Red-tagged, Re-inspection required
|
8/30/2023
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed and needs to be tested with a category 5 weight test within 90 days or less
|
8/27/2021
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
OSV is not sealed and must have a cat 5 weight test performed within 90 days or less
|
8/27/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency battery lowering device is not working. Re-inspection required
|
8/30/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency battery lowering device shall work. Re-inspection required
|
7/31/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency battery lowering device is not working. Re-inspection required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Phase I fire service bezel at key switch in lobby is illegible, need to replace
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Phase I fire service bezel wording is missing, needs to be replaced
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Phase I fire service bezel at key switch in lobby is illegible, needs to be replaced
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform relief valve testing and 15 minute standing testing to complete inspection. Re-inspection required
|
7/31/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform relief valve testing and 15 minute standing testing to complete inspection. Re-inspection required
|
8/30/2023
|