Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) Yes No Weight rods on counterweight are loose. 7/30/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 10/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Outer insulating jacket is coming off of traveling cable under car, no conductors exposed. Repair or replace
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Yes No Traveling cable is damaged in several spots and needs to be replaced. Re-inspection required
conversion conversion conversion - reinspect Yes No Car runs with car door open 4" maximum is 2" 8/6/2018
conversion conversion conversion - reinspect Yes No Cab emergency lights do not work 8/6/2018
conversion conversion n/a No No Car door restrictor does not work. 7/30/2019
conversion conversion n/a No No Weight rods loose on counter weights 7/30/2019
conversion conversion n/a No No Replace missing counterweight roller 7/30/2019
conversion conversion n/a No No Alarm bell does not work 7/30/2019