Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 11/1/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room
conversion conversion conversion - reinspect Yes No Alarm bell shall work 8/6/2018
conversion conversion conversion - reinspect Yes No Cab emergency lights do not work 8/6/2018
conversion conversion conversion - reinspect Yes No Car door restrictor does not work. 8/6/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Outer insulating jacket on traveling cable under car is coming off in several placed, no conductors exposed. Repair or replace 11/1/2023
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1001.2(e)(10) Yes Yes Safety slide only 4", minimum slide 7". Repair and/or re-adjust safeties. Red tagged elevator. 10/16/2020
A17.1-2016 : Elevators 3.16 - Traveling cables and junction boxes 8.11.2.1.3(v) No No Traveling cable insulation jacket is damaged. Repair or replace traveling cable.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Yes No Traveling cable is damaged in several spots and needs to be replaced. Re-inspection required