Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
conversion conversion conversion - reinspect x Alarm bell shall work 8/6/2018
conversion conversion conversion - reinspect x Cab emergency lights do not work 8/6/2018
conversion conversion conversion - reinspect x Car door restrictor does not work. 8/6/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Outer insulating jacket on traveling cable under car is coming off in several placed, no conductors exposed. Repair or replace
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1001.2(e)(10) x x Safety slide only 4", minimum slide 7". Repair and/or re-adjust safeties. Red tagged elevator. 10/16/2020
A17.1-2016 : Elevators 3.16 - Traveling cables and junction boxes 8.11.2.1.3(v) Traveling cable insulation jacket is damaged. Repair or replace traveling cable.