Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. 11/1/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - In phase II operation, the car doors will not stay in the open position when activated. Reinspection is required. 11/1/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emergency battery lowering device is not working, needs repaired. Re-inspection required 11/15/2023
conversion conversion n/a No No The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. 11/28/2018