Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency battery lowering device is not working, needs repaired. Re-inspection required 11/15/2023
conversion conversion n/a The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. 11/28/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. 11/1/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - In phase II operation, the car doors will not stay in the open position when activated. Reinspection is required. 11/1/2019