A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency battery lowering device is not working, needs repaired. Re-inspection required
|
11/15/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety.
|
11/1/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - In phase II operation, the car doors will not stay in the open position when activated. Reinspection is required.
|
11/1/2019
|
conversion
|
conversion
|
n/a
|
|
|
The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch.
|
11/28/2018
|