A17.1-1996 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
1206.2(c)
|
|
|
Clean car top.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean pit.
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Service or replace fire extinguisher in machine room.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Clean machine room.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Pit light does not work.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV in pit is not sealed. Perform OSV test, tag and seal upon completion. 30 day compliance. The original violation was noted on 7/21 inspection report.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Service or replace fire extinguisher in elevator machine room. Noted on 7/21 report.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The elevator machine room shall be cleaned of dust and debris. Noted on 7/21 inspection report.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The weight test shall be performed, and the overspeed valve tested before the inspection is completed.
|
|
conversion
|
conversion
|
n/a
|
|
|
Machine Room not to be used for storage of non elevator related items.
|
5/19/2020
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3a
|
|
|
Post current State certificate in machine room 5.100(2)
|
5/19/2020
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Remove all non elevator storage from machine room
|
5/19/2020
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
1001.2(b)(6)
|
|
|
Repair machine room ventilation (fan)
|
5/19/2020
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher is outdated as of 2011
|
5/19/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated certificate in machine room.
|
5/19/2020
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV in pit is not sealed. Provide testing, tag and seal upon completion. 90 day compliance.
|
2/24/2023
|