Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current State operating certificate shall be displayed in the machine room in a non-combustible frame.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No A current ABC fire extinguisher shall be provided in the machine room.
A17.1-1996 : Elevators 1.12 - Car enclosure 204 No No Replace missing handreail on left hand wall in cab.
A17.1-1996 : Elevators 1.17 - Standby power operation 207.8 Yes No Emergency power operation could not be tested.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational with 24/7 support. 7/7/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 11/2/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 5/22/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) Yes No This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on the overspeed valve within 90 days. 5/22/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certificate is required in the machine room. 7/27/2023
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 8/1/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/1/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Elevators that are equipped to operate on emergency power (noted on unit as having EP) shall be tested with no load in the car, operating on emergency power, annually. 2/7/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Adjust upthrust roller bearings for proper clearance to door hanger track. 2/16/2026
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 2/16/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 2/16/2026
A17.1-1996 : Elevators 1.12 - Car enclosure 204 No No Tighten/repair car interior handrail. 2/16/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 2/16/2026
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Emergency power operation shall be tested. 2/16/2026