Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) Yes No cables need to be shortened less than 6 ins between CW an spring 1/24/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emg lt. an bell not working 1/24/2022
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.11.2.1.1(r) Yes No door restrictor not working 1/24/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No emg. power couldnt be tested at time of insp 1/24/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emg power couldnt be done at time of insp. 4/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No runby less than 6'' between spring buffer an counterweight shorten ropes 4/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.1 - Car platform guard 2.15.9 No No need 48in toe guard unit has rope gripper 9/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) No No emg power jewel not lighting 10/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Yes No emg power lt not working 11/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.3.5 Yes No Emergency power not tested at time of inspecion. 1/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.1 - Car platform guard 2.15.9 No No toe guards are less than 48ins. 9/10/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt displayed 9/10/2024