A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
replace machine room light bulbs, they are burnt out
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
machine room light bulbs were all burnt out, replace/repair machine room lights
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
none of the machine room lights are working, repair or replace light fixtures
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3
|
x
|
x
|
the door open button did not work on fire service phase 2. did not red tag this elevator because both of the elevators that service the parking garage failed for the same reason
|
3/30/2023
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
repair cab ceiling lights, two of the fixtures are not working
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Repair/Re-Lamp in car lighting
|
|
A17.1-1996 : Elevators
|
3.26 - Broken rope, chain, or tape switch
|
210.2(f)
|
x
|
|
belt monitor is flashing error on center belt, monitor has been bypassed alowing car to run, belts are rouged. Repair the belt monitor, remove the bypass, and clean the rouge off of the belts
|
10/20/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Missing Phase 1 Instructions at main egress fixture
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room is to be updated every year with the current certificate
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.11.2.1.3(cc)
|
|
|
the hoist belt monitor is flashing an error that 2 of the belts are failing. Check the belts and if they test good repair the monitor, if the belts test bad replace the hoist belts
|
3/30/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(c)
|
|
|
a monthly fire service test log is to be posted in the machine room and filled out monthly
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide updated fire extinguisher
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Owner to keep updated monthly fire service records
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.3.9
|
x
|
|
Repair/replace remote governor reset solenoid - 2.7.6.5: means necessary for testing
|
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13 Door Systems
|
|
|
Missing upthrust at 2nd floor door
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Keep pit free of dust and debris
|
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean the car top
|
|
conversion
|
conversion
|
n/a
|
|
|
replace phase 1 keyswitch collar, can no longer read the woords on, off, bypass, or fire service
|
|
conversion
|
conversion
|
n/a
|
|
|
landing 2 is missing the upthrust roller on the leading edge of the hoistway door on the fast panel
|
|
conversion
|
conversion
|
n/a
|
|
|
governor tail sheave switch arm is not between the pins on the tail sheave
|
|