Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting machine room lights are not working, replace burnt out light bulbs or repair broken fixtures as needed
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Repair overhead lighting
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 x x The door open button did not work on fire service phase 2 operation. did not red tag elevator because both of the elevators that service the parking garage failed to open the doors on fire service phase 2 3/30/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 repair cab ceiling lights, one of the fixtures is not working
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Repair/Re-lamp in car lighting
A17.1-1996 : Elevators 3.26 - Broken rope, chain, or tape switch 210.2(f) x hoist belt monitor is flashing error on one of the blets, the belts are rouged, the belt monitor has been bypassed alowing the car to run, repair the belt monitor and remove the bypass and clean the rouge off of the belts 10/20/2020
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the copy of the state operating certificate is to be updated every year with the current certificate and posted in the machine room
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) hoist belt monitor is flashing error that one of the hoist belts is failing. Check that the belts test good and repair the belt monitor or if the belt tests bad replace the hoist belts 3/30/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) the monthly fire service test log is to be posted in the machine room
A17.1-2016 : Elevators 2.4 - Machine space 8.6.1.6.5 Fire Extinguishers Provide updated fire extinguisher
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Owner to keep updated monthly fire service log
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 x Repair/replace remote governor reset solenoid - 2.7.6.5: provide means for testing
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Keep the pit clean and free of dirt and debris
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Top of Cars Clean the car top
conversion conversion conversion - reinspect x the coated steel belt monitor is flashing error that says the belts need to be replaced 7/27/2018
conversion conversion n/a the governor tail sheave switch is not mounted carrectly, the switch arm is not between the two tail sheave studs so it will not trip in both the up and down directions