A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Elevator cab phone does not work, phone line has no power. Re-inspection required
|
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
OSV is not sealed. Perform OSV test on or before next annual inspection.
|
12/15/2021
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
Yes
|
No
|
Emergency battery lowering, ERU, inoperative.
|
12/15/2021
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Provide on-site maintenance control program.
|
12/15/2021
|