Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. (The phone calls out, but is never answered) 3/19/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. There is no dial tone. 5/7/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Fire service testing shall be documented monthly. Only one month was documented in 2023. 5/7/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log, and fire service log recorded monthly. The log is not being filled out. 2/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 4/19/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve and shall be tested with the rated load on or before the next annual inspection. 5/7/2024