A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
All machine room enclosures shall have self-locking door and shall be operable from the interior space without the use of a key.
|
6/9/2022
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
1001.2(c)(16)
|
|
|
Seal all holes in the hoistway and remove all abandoned electrical wiring in hoistway.
|
6/9/2022
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit ladder shall extend not less than 42" above the sill of the access door. The present ladder does not meet this requirement.
|
6/9/2022
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Receptacle in the pit shall be ground fault protected.
|
6/9/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
A record of findings for firefighters' service operation is required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
|
6/9/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
There is a smoke detector and a heat detector at the top of the hoistway, there is also a heat detector in the machine room. Since there is no shunt trip disconnect in the machine room and there are no sprinklers in the two areas mentioned, verify that these detectors do not affect the operation of the elevator.
|
6/9/2022
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Install a code date plate. It shall read: "A17.1-1996"
|
6/9/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
6/9/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
4/1/2025
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
6/9/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
6/9/2022
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
6/9/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The alarm bell shall be operational on auxiliary power.
|
5/5/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
The in car emergency lighting shall be operational.
|
5/5/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light is not working.
|
2/7/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell is not working.
|
2/7/2024
|
A17.1-1996 : Elevators
|
2.37 - Pressure Switch
|
306.14
|
x
|
|
The pressure switch does not work.
|
5/23/2022
|
A17.1-1996 : Elevators
|
2.37 Pressure switch
|
306.14 Pressure switch
|
x
|
|
The pressure switch shall be operational according to A17.1 - 306.14
|
4/6/2020
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
|
x
|
|
This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed and witnessed within 90 days.
|
8/8/2023
|