Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes Yes The shackled ends of the hoist ropes are striking the counterweight side of the deflector sheave. This in turn, results in the hoist rope to jump its groove. Repair/reinspection required before continuation of testing and returning the elevator to operational service. 4/2/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate in the elevator machine room. 11/3/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency lighting shall be operational. 11/22/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No The in car emergency alarm bell shall operate with 110v source removed. 11/22/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be operational. 8/7/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit lighting shall be operational. 12/11/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. 12/11/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace the missing bottom floor pickup rollers. 12/11/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/11/2025