MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
12/20/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
|
|
No emergency light
|
1/25/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
No emergency alarm
|
9/21/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Provide maintenance control plan on site posted on controller
|
1/25/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Need code data plate conforming to sec 8.9
|
12/20/2021
|