Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No Emergency communications/phone in car not working.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency communications/phone in car not working reinspection item 30 day maximum 9/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Emergency power indicator inoperative 4/21/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 3/24/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 3/24/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 5/13/2019
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(t) Yes No Repair brakes failed 125% red tagged unit reinspection required 4/8/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service and document on log in machine room 3/24/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 3/24/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service and document on log in machine room 3/24/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Generator/standby power needs to be tested reinspection item maximum 30 days to complete 9/10/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No This elevator is equipped with emergency power. The operation of elevators equipped with standby or emergency power shall be tested annually to determine conformance with the applicable requirements. The generator technician said he was unable to perform the test, and needs to order replacement parts. 3/24/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Could not get generator started
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces No No Remove non elevator storage from machine room 3/24/2026