Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No Need testing procedures in the MCP on or before 1/1/22 11/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Need oil collection container in pit, not to exceed 5 gallon capacity 11/14/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 11/14/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No Need testing procedures in the MCP on or before 1/1/22 3/26/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Need oil collection container in pit, not to exceed 5 gallon capacity 3/26/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/26/2026
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Yes No Test overspeed valve 7/15/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Auxiliary power lowering operation is not functional. 11/14/2025
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) Yes No Overspeed valve is not sealed or tagged. 5 year test with full load shall be performed. (2nd Notice) 11/14/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Auxiliary power lowering operation is not functional. 4/1/2026
conversion conversion conversion - reinspect Yes No emergency phone not working 11/27/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Yes No Full load overspeed valve test past due 90 max to complete 11/19/2024