Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) repair the front car door restrictor, the hook did not catch the latch 7/21/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Perform monthly fire service test and post a log in the machine room 7/21/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x emergency light battery is dead, replace batteries and verify operation 3/11/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.3a(8) Visual and audible signal x repair the phase 1 audible signal, it did not work 3/11/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x x Repair phase one keyswitch did not work, repair keyswitch 11/4/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Recovery pump in the elevator pit for hydraulic oil not allowed per memo from the state, memo 006 (A17.1 8.6.5.5)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Repair the front door restrictor so that it works 11/4/2024