MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
12/6/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Perform monthly fire service test and post a log in the machine room
|
7/21/2020
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(5) Oil Leakage Collection
|
|
|
recovery pump in the elevator pit is not allowed per memo 006 from the state of Missouri, replace with bucket
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
repair the emergency lights, they did not come on, the bell worked
|
7/21/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Recovery pump in the elevator pit for hydraulic oil not allowed per memo from the state, memo 006 (A17.1 8.6.5.5)
|
|